Ultra-Dek® SPECIAL ERECTION TECHNIQUES


UL 90 LIGHT TRANSMITTING PANEL INSTALLATION

The light transmitting panel is designed to be installed in a manner similar to a panel application, utilizing the same panel lap (3’) and fastener layout.

NOTE

The standard light transmitting panel is 10'- 3" long, designed for applications with purlin spacing no greater than 5'- 0" 3/16" (1:12 slope). Maximum width of purlin flange to be 3 1/2".

UL 90 light transmitting panels are shipped with a stiffener plate and ten self-drilling #1 E fasteners for each light transmitting panel.

The stiffener plate is to be field installed on the bottom side of the light transmitting panel over the mid-purlin.

The light transmitting panel rivets that obstruct the stiffener plate must be drilled out and replaced with Fastener #1 E in five places on each side. THIS STIFFENER PLATE MUST BE EXACTLY CENTERED OVER THE MID-PURLIN SO THAT THE THERMAL MOVEMENT OF THE SYSTEM IS NOT RESTRAINED BY THE PURLIN.

NOTE:

THE WASHERS REQUIRED AT THE DOWNSLOPE END OF THE LIGHT TRANSMITFING PANEL ARE #14 x 1 1/8" BONDED

IMPORTANT NOTE Floating Clip must be used on UL 90 rated light transmitting panels.

WARNING: These light transmitting panels are not designed or intended to bear the weight of any person walking, stepping, standing or resting on them. THE MANUFACTURER DISCLAIMS ANY WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, that any person can safely walk, step, stand or rest on or near these light transmitting panels or that they comply with any OSHA regulation.