UL 90 REQUIREMENTS |
|
Construction #30 |
|
26 MSG Min. Gauge "PBR" Panel Over Purlins at 5- 0 1/4" O.C. |
- For Class 90 -
Panel to purlin connections to be #14 Hex Head with a 5/8" O.D. washer
in a 4-8-4-8 in. pattern. Panel to panel connection to be 20" O.C. with
faster located over each purlin.
-
Purlins - No. 14
MSG min. gauge steel, (55,000 psi min. yield strength.)
|
|
Construction #79 |
|
26 MSG Min. Gauge "PBR" Panel Over Purlins at 5'- 0 1/4" O.C. |
- Panel Fasteners -
Panel to purlin connections to be #14 Hex Head with a 5/8" O.D. washer,
6" O.C. in 5-7-5-7 in. pattern. Endlap spacing to be 6 in. O.C. Spacing
for panel to panel connection to be 20" O.C..
-
Purlins - No. 16
MSG Min. gauge steel. (55,000 psi Min. yield strength); or min. H series
open web steel joists.
|
|
Construction #161 |
|
26 MSG Min. Gauge "PBR" Panel Over Purlins at 5'-0 1/4" O.C. |
- Panel Fasteners -
Panel to purlin connections to be 12-14x1" self-drilling Hex Head with
a 5/8" O.D. washer, 12" O.C.. Spacing at endlap to be in a 5-7-5-7
in. pattern. Spacing for panel to panel connection to be 20" O.C. with
a fastener located over each purlin.
-
Purlins - No. 16
MSG Min. gauge steel. (55,000 psi Min. yield strength).
|
|
Construction #542 |
|
26 MSG min. Gauge "PBR" Panel Over Purlins at 5'- 0
3/16" O.C. |
- Panel Fasteners -
Panel to purlin connections to be 12-14x1" self-drilling Hex Head with
a 5/8" O.D. washer,12" O.C.. Spacing at endlap to be in a 5-7-5-7
in. pattern. Spacing for panel to panel connection to be 20" O.C.. with
a fastener located over each purlin.
- Building Units - Translucent
Panels.
- Translucent Panel Rib
and Purlin Reinforcement - See UL 90 light transmitting panel
installation instructions.
-
Purlins - No. 16
MSG min. gauge steel. (55,000 psi min. yield strength).
|
|
IMPACT RESISTANCE |
|
"PBR" panels carry a Class 4
rating under UL-2218 "Test Standard For Impact Resistance" |
|
FIRE RESISTANCE RATING |
|
Class A |
-
Deck: NC
Incline: Unlimited The panel qualifies for a Class A Fire Rating in compliance
with Underwriters Laboratories Standard UL-263 when installed over a non-combustible substrate. A Class C
Fire Rating will be qualified for over a combustible substrate.
|
|
Look for classification marking on product. |
|
CAUTION
The above listings are summaries of
Construction Numbers. For UL 90 rated roof requirements and complete design
information, see the Underwriters Laboratories Building Materials Directory. If
you have any questions, call ASBC before proceeding.
|
|
Back Next |